Experimental performance analysis of an ejector refrigeration cycle in cascade refrigeration cycle
Вантажиться...
Дата
2020
Автори
Назва журналу
Номер ISSN
Назва тому
Видавець
Анотація
The exhaust heat from compressor is removed by a heat driven ejector
refrigeration cycle (ERC) in the compression - ejector cascade refrigeration system,
which can effectively improve system performance by reducing the condensation
pressure and the electric power consumption. The working conditions of ERC
extremely affect the performance of cascade system. In order to explore the best
working conditions of the system, a test rig of ERC operating with refrigerant R245fa
was design and built to investigate the performance carefully. Thermal coefficient of
performance (COPth), entrainment ratio and cooling capacity of ERC at various
operating conditions were measured and analyzed. Some useful conclusions could be
obtained from the experimental data. ERC with high evaporation temperature has
significantly better performance and hold great application potential in different
cascade/hybrid systems. With the evaporation temperature of ERC increasing from
15°C to 30°C, its COPth increases from 0.19 to 0.45 by 137.1% and the critical
condensation temperature also increases from 39°C to 44°C. Higher COPth and
cooling capacity occur at the lower generation temperature, however, the critical
condensation temperature keeps relatively low which is not conducive to working at
high ambient temperatures. Experimental results and analysis in this study are helpful
to the application and working condition optimization of ERC in cascade/hybrid
refrigeration systems.
Опис
Xinyue Xao Experimental performance analysis of an ejector refrigeration cycle in cascade refrigeration cycle / Xinyue Xao, Yifan Zhou, Yini Pan ; supervisor Guangming Chen // Black Sea Science 2020: proc. of the Intern. Competition of Student Scientific Works / Odessa National Academy of Food Technologies; eds. B. Yegorov, M. Mardar [et al.]. – Odessa: ONAFT, 2020. – P. 473–490 : tabl., fig. – Ref.: 25 tit.
Ключові слова
ejector refrigeration cycle, cascade refrigeration system, experiment, performance